The Central Electricity Authority (CEA) has issued a standard operating procedure (SOP) to guide wind power projects replacing old turbines with modern ones while running both together. The SOP covers nationwide repowering projects and partially commissioned plants using approved grid connectivity up to granted limits, subject to system feasibility. 

Furthermore, in steady-state grid studies, non-compliant old turbines are treated as having zero power output until repowering ends, project design life finishes, or power or wheeling agreements expire. After that milestone, every turbine at the site must meet CEA connectivity rules or be retired or repowered. 

Additionally, the developers must submit detailed root mean square and electromagnetic transient simulation models for reactive power and power quality checks, plus aggregated models for dynamic studies of new turbines. Required mitigation equipment like harmonic filters or reactive power devices must be installed before grid connection, with harmonic filter compliance allowed in batches of at least 33 percent capacity. Power quality meters are also mandatory at the point of interconnection, alongside disturbance or digital fault recorders at the point of interconnection or post-February 2019 turbines. Model validation for the wind turbines will also happen in phases, starting with batches of at least 33 percent capacity, backed by periodic meter and fault data until full repowering is complete.